AP7724Features
Rack ATS, 2U 230V, 32A, IEC309-32A In, (16)C13, (2)C19 Out
-
Local Current Monitoring Display
The aggregate current draw per rack PDU is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. (Available on designated SKUs only)
Rack-mount Transfer SwitchesFeatures & Benefits
Marketing Features
-
Rack-Mountable
Occupys only 1U of valuable rack space. Puts the power where it is needed most - in the rack near the equipment.
-
Dual Input Power Sources
Supplies redundant AC power to connected equipment. Two AC lines power the unit and if the primary AC power fails, the unit will automatically switch to the alternative power source.
-
Information Displays
Indicates the status of the AC sources powering the units, as well as indicates which source is set as the primary source and which source is currently supplying power to the load. This provides a visual depiction of the power flow from the input to the load. This allows the user to quickly glance at the power flow and status of the input sources without connecting to the unit.
Agility
-
Wide range of input and output connections
Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.
Availability
-
Remote Management Capabilities
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.
-
Dual Input Power Sources
Supplies redundant AC power to connected equipment. Two AC lines power the unit and if the primary AC power fails, the unit will automatically switch to the alternative power source.
Output
Input
-
Nominal Input Voltage
200V , 208V , 230V
-
Input frequency
50/60 Hz
-
Input Connections
IEC 309 32A 2P+E
-
Cord Length
2.44meters
-
Number of Power Cords
2
-
Maximum Input Current
32A
-
Maximum Line Current
32A
Physical
-
Maximum Height
88mm , 8.8cm
-
Maximum Width
432mm , 43.2cm
-
Maximum Depth
236mm , 23.6cm
-
Rack Height
2U
-
Net Weight
6.86kg
-
Shipping weight
9.36kg
-
Shipping Height
184mm , 18.4cm
-
Shipping Width
613mm , 61.3cm
-
Shipping Depth
356mm , 35.6cm
Environmental
Conformance
-
Approvals
EN 55022 Class A, FCC Part 15 Class A
-
Standard warranty
2 years repair or replace
Sustainable Offer Status
-
RoHS
Compliant
-
REACH
REACH: Contains No SVHCs
-
PEP
Available in Documentation tab
-
EOLI
Available in Documentation tab
-
Battery Directive
Compliant
-
Battery Notes
ts_Battery_Notes